Prelab 2019 Refrigeration Lab Data Loop Efficiency & Effectivness I need : Abstract, Result and Discussion and Conclusion for this report ” prelab 2019″u n

Prelab 2019 Refrigeration Lab Data Loop Efficiency & Effectivness I need : Abstract, Result and Discussion and Conclusion for this report ” prelab 2019″u need to follow the objective on the report in order to know what to do. use my data “Refrigeration lab data r6” and compare it with with original data “refrigeration Data” using excel.lab manual is provided. i provided an old report (_Refrigeration.pdf.) if that helps u but no copying from them at all ( i can add more) . i can provide some info and guidelines about abstract or results and discussion. all figures and tables (e.g. t-test) from excel must be in the report in appendix section.u might use the old reports but u may paraphrase. R2_Bandar
Comparing the Coefficient of Performance
for Varying Flowrates of Refrigerant
through the Refrigeration System
Group R2
Abdulaziz Fahad
Giovanna Caruso
Jason Ellis
Written by:
Bandar Alotibi
4/20/2017
R2_Bandar
Abstract
The process of refrigeration is an essential process in the industry. This process is
accomplished by the use of a working fluid and mechanical energy to facilitate the transfer of heat
from cold region to a hotter region. The process is affected by multiple parameters but in this paper
of interest is the effect of the compressor setting and the refrigerant flow on the coefficient of
performance (COP) of the refrigeration cycle. For this experiment the relationship between compressor
speed and coefficient performance of the Armfield RA-1 MKII was determined. The performance of a
refrigeration equipment can be determined using the coefficient of performance that relates the amount
of heat transferred per unit of work added to the system. From the data gathered, maximum COP was
achieved at 1% compressor setting with a value of 8.2 ± 0.32 while the lowest at the 100% setting
with a value of 4.8 ± 0.38. It could be concluded that process is more efficient at low compressor
settings with low refrigerant flow thus resulting in low effluent pressure. This is indicative of the
overdesigned refrigeration cycle for the process simulated thus it could be used for a more
intensive cooling process. . It was determined that with a 95% confidence level the sample means were
not equal. Therefore, increasing the compressor speed had a significant effect on the coefficient of
performance of the RA-1 MKII refrigeration unit.
Introduction
Refrigeration is the process of lowering the temperature of an enclosed space by forcefully
removing the heat and transferring it elsewhere by means of a working fluid. Traditionally the
process of refrigeration was made to occur naturally by means of temperature gradient where heat
moved freely from an area of high temperature to an area of low temperature as applied in ice
boxes [1]. Currently, refrigeration is accomplished by means of mechanical work which aids the
transfer of heat through a cycle. The purpose of refrigeration is to create a low temperature zone
in the space or object heat is absorbed [1]. The principle is applied in air conditioning equipment
to provide the required cool environment in rooms for human comfort. The most popular use of
refrigeration however is in preservation of perishables such as in homes, supermarkets and hotels.
The goods are kept at low temperatures to discourage the growth of bacteria. In medicine,
refrigeration is employed to provide very low temperatures for preservation of drugs and body
R2_Bandar
tissue samples. Most industrial cooling processes such as condensation of gases before storage
and transportation and the cold treatment of materials also use the concept of refrigeration. The
Objective of the experiment is to establish how refrigeration loop coefficient of performance is
affected by varying the compressor speed, and to determine whether there is an optimum operation
condition that would lead to the highest coefficient of performance.
Theory
Refrigerators are the heat transfer from a low temperature sink to a high temperature
source. It uses refrigerant in cyclic devices to remove heat from the cold medium. The refrigeration
cycle obeys the first law of thermodynamics. Such that energy can neither be created nor destroyed
but it can only be transferred from one medium to another.
= +
(Equation 1)
The maximum efficiency of a cycle and with less work used is the ideal case of the Carnot
refrigeration cycle. The Carnot cycle
consists of four processes: isentropic compression in a
compressor, isobaric heat rejection in a condenser, throttling in an expansion device, and isobaric
heat absorption in an evaporator. Since this process will not be reversible, an actual vaporcompression refrigeration cycle would be more likely to look at. The fluid friction and heat
transfers to or from the surroundings are the biggest contributors to the process being irreversible.
Both of these have effects on the entropy of the system.
To find the efficiency of the refrigerator, the coefficient of performance (COP). The COP
is the compares the desired output with the required input. It is always a positive number and can
be greater than one. The purpose of the refrigerator is to remove heat from a cold space and release
it into the surrounding [1]. COP can then be found by:
=

(Equation 2)
With as the amount of heat absorbed from the water and is the power used by the
compressor. The can be found by:
R2_Bandar
= ̇(ℎ1 − ℎ4 )
(Equation 3)
with the ̇ is the mass flow rate of the liquid and ℎ1 and ℎ4 are the enthalpies corresponding to
points 1 and 4, Figure 1.
Figure 1: A pressure vs enthalpy diagram for a refrigeration cycle [2].
Methods
Apparatus
The unit used in the experiment was the RA1-MKII, which used a computer based interface
to control the cycle. Below is a schematic of the unit and the locations of the sensors which were
presented in the software. Along with Figure 2, Figure A1 illustrates the unit used for better
understanding.
R2_Bandar
Figure 2: Schematic Diagram of the RA1-MKII Showing the places of the sensors with respect
to the cycle [2].
Experimental Design
The coefficients of performance were calculated using a refrigeration system described in
the Armfield Refrigeration unit instruction manual for compressor speeds of 1, 50, and 100%. The
experiment was repeated three times to compare the results statistically. The Armfield RA1-MKII
software generated a table showing the COP and P2 as functions of time at intervals of 10 seconds
for two minute. The COP values were then compared using statistical analysis at each speed
explained in the methods of analysis. Two plots were generated: COP versus compressor speed
and COP versus P2 to determine the effect that compressor speed and pressure have on the COP.
Results and Discussion
The obtained results are graphically presented in the succeeding figures in order to establish
a trend for the relationship of the different variables such as the COP, compressor setting,
refrigerant flow, and P2 (pressure).
R2_Bandar
From the data gathered in table 1 to table 6, it can been seen that the coefficient of performance is
highly dependent on the refrigerant flow and subsequently the pressure of the effluent from the
compressor.
From Figure 3, an inverse relationship could be seen between the COP and the compressor setting
thus a decrease in the COP is observed with an increase in the compressor setting. The declining
trend is an indication that the compressor may be overdesigned for the process thus requires
minimal setting of the compressor.
A plot of COP against Compressor Setting
9.0
8.0
7.0
COP
6.0
5.0
4.0
3.0
2.0
1.0
0.0
0%
20%
40%
60%
80%
100%
120%
Compressor Setting
Figure 3: A graph of the coefficient of performance (COP) vs. compressor setting
A similar trend is observed with the relationship of the COP with the refrigerant flow. The COP
decreases with an increase in the refrigerant flow thus indicating that the process simulated actually
requires minimal refrigerant for the set temperature. This similar trend is understandable given that
the relationship between the two parameters which is shown in Figure 5. A direct relationship is
established between the compressor setting and the refrigerant flow which is expected between the
two parameters since the compressor drives the refrigerant (working fluid) into the system.
R2_Bandar
9.0
8.0
7.0
COP
6.0
5.0
4.0
3.0
2.0
1.0
0.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
Refrigerant Flow (L/hr)
Figure 4: A graph of the coefficient of performance (COP) vs. refrigerant flow
30.0
REfrigerant Flow (L/hr)
25.0
20.0
15.0
10.0
5.0
0.0
0%
20%
40%
60%
80%
100%
120%
Compressor Setting
Figure 5: A graph presenting the relationship between the refrigerant flow and the compressor
setting.
R2_Bandar
8.5
8.0
7.5
COP
7.0
6.5
6.0
5.5
5.0
4.5
4.0
6.0
6.5
7.0
7.5
8.0
P2 (bar)
Figure 6: A graph of the relationship between the coefficient of performance (COP) and the
pressure from the compressor to the condenser (P2)
The relationship between the effluent pressure and the COP follows a similar decreasing trend sa
with the refrigerant flow and the compressor setting. This is evident of the overdesigned
refrigeration cycle for the process.
T-tests were conducted among the trials and it can be concluded that the samples from the different
compressor settings present different values and are not of the same sample population thus gives
variance on the experimental set-up. This is backed up by the p-values from table 10 which are
0.000837 between the COPs at 1% and 50% and 0.012889 for the 50% and 100% trials. The trends
observed between the different settings thus could be considered valid and varied enough to be
conclusive.
Conclusion
The objective of the experiment was achieved since the relationship between the COP and
coefficient performance of the Armfield RA-1 MKII was determined. The COP value achieved at
1% compressor setting had a value of 8.2 ± 0.32 while the lowest achieved value was at 100%
setting that had a value of 4.8 ± 0.39. It could be concluded that process is more efficient at low
compressor settings with low refrigerant flow thus resulting in low effluent pressure. This is
indicative of the overdesigned refrigeration cycle for the process simulated. For better results to
R2_Bandar
be obtained, more time should be given to the compressor to allow it to settle before data is taken
after each interval of measurements done. Besides, the data could be taken over longer periods of
time.
R2_Bandar
References
[1] Cengel, Yunus A., John M. Cimbala, and Robert H. Turner. Fundamentals of Thermalfluidsciences. New York: McGraw-Hill Higher Education, 2012. Print.
[2] Armfield Ltd. Vapor-Compression Refrigeration Unit: Instruction Manual. Issue 2. August
2013. Print. RA1:MkII.
Appendix
Experimental Protocol
1.
Verify the USB connection exists between the RA1-MK11 unit and the PC.
2.
Check the RCD/combined circuit breaker is on – in the up position
3.
Switch the unit on by flipping the power switch on the console.
4.
Check to see what the temperature, pressure, and other values are; should be about ambient.
5.
Set Pump 1 to desired speed and Pump 2 to desired speed. The condenser water pump
(Pump 1) should be set to 40% and the evaporator water pump (Pump 2) should be 60%.
6.
Verify water is flowing through the compressor and evaporator. Typically 1.5L/min and
5.5L/min respectively on the mimic diagram
7.
Set the compressor motor speed to 10%, about 2000RPM, then click compressor on, on the
screen. Allow system 30 seconds to reach 2000 RPM set point. Check the flowmeter F3 on RA1MK11 to ensure working fluid flows through the system
8.
Set the sample options as ‘Automatic / 10 second intervals’ and click GO. The readings
from the sensors will now be recorded.
9.
While looking at the graphs of T1, T3, and T7 on the Y-axis and P1 & P2 on the secondary
Y-axis, allow the system until the values are reasonably steady i.e. the changes within 5%.
10. Record the refrigerant flow rate on the variable area flowmeter F3 and enter the value on the
mimic diagram.
11. Increase the compressor speed to 20% around 2460 RPM, and repeat steps 9 and 10.
12. Repeat this process for 40% (2945 RPM), 60% (3430 RPM), 80% (3915 RPM) and 100%
(4400 RPM).
13. Set the compressor speed back to 50% and let the system reach dynamic equilibrium
R2_Bandar
14. Click the ‘Stop button’ to discontinue recording data and next click ‘Compressor on’ to stop
the compressor.
Method of Analysis
The null hypothesis for the experiment was that the Coefficient of Performance for 1, 50 and
100% compressor speeds respectively could be explained by random chance.
Once all the data were obtained from the refrigeration unit, the optimum operation condition was
be determined. The compressor’s speed which lead to the highest COP was determined to be the
optimum setting for the unit. Moreover, the set of COPs from the three trials at the same speed
were compared statistically to another set at a different speed. This is to analyze the effect of
compressor speed on the COP. Out of all the data, two plots were generated, COP versus
compressor speed and COP versus the outlet pressure from the compressor (P2).
Safety
Safety precautionary measures and regulations must be observed to guarantee the safety of
the users and the condition of the equipment.
An immediate risk in this experiment setting is the presence of hot surfaces which can
cause serious burns. It is recommended that users have to allow time for the equipment to cool
before handling it. The ‘hot surfaces’ labeled surfaces should never be touched or brought close to
flammable materials.
Since the equipment operates on an electrical supply, electrical safety measures have to be
adhered to. The RA1-MKII should be operated with the prescribed frequency and voltage and it
should be made certain that all the panels are in place before connection. The refrigeration unit is
fitted with a Residual Current Device (RCD) which switches off electrical supply in case the
system becomes electrically flawed. This device should be checked regularly and maintained in
good working condition.
The equipment contains rotating parts which demands special safety attention. It should be
ensured that the protective guards against these parts are in place before operation. The users are
required to clear off from the rotating parts when in operation and refrain from inserting any object
past the protective guards. The parts must be left to come to rest after switching off the equipment
R2_Bandar
before attending to them. By fact that the equipment is heavy and hot, it should be maintained in
a strong frame and handled carefully. The equipment should not be left to run unattended.
Electrical safety – the Armfields RAI-MKII refrigeration unit should be operated on the
specified voltage and frequency. The Residual Current Device (RCD) should be checked regularly
to ensure that it is functioning well. The experiment involves the use of water and care should be
taken for possible spillage. All electrical connections and adjacent devices should be secured to
avoid water from reaching them.
Raw data sheet.
Figure A1: T-s phase diagram for the cycle [2].
R2_Bandar
A. Raw Data
Table 1: Raw data for Trail 1 at 1% compressor speed
Table 2: Raw data for Trial 1 at 50% compressor setting
Table 3: Raw data for Trial 1 at 100% compressor setting
R2_Bandar
Table 4: Raw data for Trial 2 at 1% compressor setting
Table 5: Raw data for Trial 2 at 50% compression setting
Table 6: Raw data for Trial 2 at 100% compression setting
R2_Bandar
Table 7: Raw data for Trial 3 at 1% compressor setting
Table 8: Raw data for Trial 3 at 50% compressor setting
Table 9: Raw data for Trial 3 at 100% compressor setting
R2_Bandar
B. T-tests
Table 10: t-test comparing 1% and 50%compressor settings
t-Test: Two-Sample Assuming Unequal Variances
COP @
1%
8.236167
0.102268
3
Mean
Variance
Observations
Hypothesized Mean
Difference
df
t Stat
P(T
Purchase answer to see full
attachment

"Order a similar paper and get 100% plagiarism free, professional written paper now!"

Order Now